|
Transformers
Transformers are simple devices that, in low
voltage lighting applications, step down or reduce 120 volt A.C. house
current to 12 volt A.C. current. You may remember from elementary
science class that this is accomplished by induction. There are two
coils around a core of iron plates. The house or line current passes
through the primary coil creating a magnetic field. The second coil,
called the secondary coil is energized by the magnetic force created by
the primary coil. Depending on the number of turns of the secondary coil
relative to the primary coil, the voltage will be reduced at the output
terminals of the secondary coil. This is true when the number of turns
on the secondary coil is less than the turns on the primary coil. If
there were more, the voltage would be higher and you would have a step
up transformer. To reduce 120 volts to 12 volts the primary coil has 10
times the turns of the secondary coil.
Typical low
voltage transformers are designed to reduce 120 volt line voltage to a
secondary, or output voltage of 12 volts. However the transformer has no
way of knowing the line voltage. It simply reduces the current by a
factor of 10. So if the line voltage was 115 volts, the secondary
voltage would be only 11.5 volts. Conversely, if the line voltage was
130 volts, the transformer would produce 13 volts. Line voltage may vary
with time of day and when other electrical loads are on the system. For
this reason it is important to measure the line voltage at the
transformer at the same times that the transformer will be in use.
Remember from the lamp section, a small change in voltage can make a
significant difference in lamp life and output.
As discussed
earlier, voltage will decrease the further the current has to travel. In
order to compensate for this loss and the variations in line voltage,
some transformers offer several output voltages. These transformers are
generally known as multi-tap transformers and may offer voltage outputs
ranging from 10 volts to 14 volts. This is accomplished by having leads
coming off the primary or secondary coil at various points near the end
of the coil to produce several different voltages. This is a valuable
feature for a system designer wanting to have better control over light
output and lamp life.
There are also
buck (reduce the voltage) and boost (increase the voltage) transformers
that can also be used to change the line voltage a small amount. If you
had a situation where the line voltage was typically 110 volts, the
landscape lighting transformer would have a normal output of only 11
volts. This reduced output could be offset by using a multi-tap
transformer (the 14 volt lug would output 12.8 volts and the 13 volt lug
would have an output of about 11.9 volts.) or you could have an
electrician install a 10% boost transformer (110 volts + 10% = 121
volts) .You can correct higher than 120 volt situations in the same way
by using a buck transformer to reduce the current.
Some companies
also offer these transformers to boost voltage on the secondary side.
This type of transformer is designed to be buried in the ground as part
of the circuit. The typical boost is 20% to 25%. Therefore if the voltage drop
is down to 10 volts at the fixture, installing a booster transformer
ahead of the fixture could increase the voltage to 12 or more volts.
It is
important to understand that transformers can not stabilize voltage
variations. They simply transfer the current at a fixed ratio and do not
sense changes. There is equipment to handle this problem, but it is
typically too expensive and unnecessary for landscape lighting
applications.
Transformers
are offered with and without a cabinet. Those without an enclosure are
attached to an electrical box and wired directly to the line voltage
source. This type of transformer should be installed by a licensed
electrician.
Transformers built into an enclosure are connected to the
line voltage source with a standard 6’ plug and cord set. When the
transformer is mounted outside, the outlet used to power
it should be protected by a Ground Fault Circuit Interrupter (GFCI)
device. This device will shut off the current instantly when it
senses an over current situation. They are designed to protect people
from electrical shock while the breaker protects the building and
electrical system. GFCIs are available for individual outlets or as part
of the circuit breaker that protects the entire electrical circuit. This
type of GFCI is located in the electrical service panel and should only
be serviced by a licensed electrician.
The
transformer enclosure may be made of plastic, composites, painted steel,
or stainless steel. The least expensive are plastic models that are
frequently completely sealed with a single output cable used to connect
to the lighting system. Steel cabinets generally open to allow for the
use of controls and have electrical screw down lugs to attach the wires
from the lighting circuits. If the transformer is multi-tap, there will
be several lugs, each marked with the output voltage.
Composites
cases are used for direct burial type transformers. These units can be
used when the lighting system is at a distance so far from the power
source that there is a significant voltage drop that cannot be
compensated for with larger wire. Because the location of the
transformer in this situation is typically away from a structure, it is
often convenient to bury the transformer. By running line voltage to the
area and connecting it directly to the transformer, the voltage drop
problem is eliminated. When using this type of power unit make sure that
all installation requirements are met, particularly with regard to
access and drainage.
It should be
noted that not all enclosed transformers are suitable for use indoors.
This may sound strange, indoor use having more protection from the
weather, but it has to do with heat. This is not a problem when the
transformer is in the open air, however if not designed for indoor use,
the transformer could overheat. If the transformer is to be located
indoors make sure that it is rated for that type of location.
Quality
transformers are made with protection from over load and short circuit
situations. This is an important safety feature. The transformer is
protected on the line voltage side by the fuses or breakers in the
electrical service panel for the building. But the secondary side of the
transformer is not connected to that system. It is energized by
induction not direct contact so the breaker does not protect it. Quality
transformers protect the secondary side by running the low voltage
through a breaker or fuse.
Finally,
and most importantly, make sure that the transformer has an Underwriters
Laboratory (UL) listing for the intended use. Transformers (power units)
may be listed for indoor use only, outdoor use only, indoor/outdoor use,
or for use with submersible fixtures or pumps. UL Listed products will
have the UL symbol and be marked for the type of use along with a
control number on the device. The UL standard for landscape lighting is
UL 1838, “Low Voltage Landscape Lighting Systems.” |