HOME
Why Light
Lamps
Fixtures
Transformers
Controls
Wire & Connectors
Project Design
Lighting Techniques
Lamp Selection
Fixture Selection
Circuit Design
Safety
Installation
Maintenance
Troubleshooting
About Us
Resources

 

Circuit Design
A good starting point in circuit design is to use a general rule of thumb of limiting circuits to 100 watts or less as determined by adding the wattage of all of the lamps on the circuit. If the circuit has more than 100 watts and/or is longer than 100 feet when using 12 gauge wire you should calculate for voltage drop. For good lamp life and performance the voltage at the lamp should measure between 10.5 volts and 12 volts for standard filament lamps and 10.8 volts to 12 volts for halogen lamps. Halogen lamps operated at less than 10.8 volts will have a significantly shorter life.

 

Calculating Voltage Drop

As electrical energy passes through a wire it looses a little bit of voltage due to the resistance of the wire. This reduction is called voltage drop. Considering that it is thought of as the most important thing to understand about low voltage wiring, you would think that by now there was total agreement on how to calculate it. That’s not the case. There are several ways to calculate voltage drop and they often result in significantly different answers. That’s the bad news. The good news is that in most cases close enough is good enough. Although voltage drop is calculated with precision (two or three decimal places), the assumptions that the calculations are based on are not that precise. In addition, most people will not notice the difference in fairly significant differences of measured illumination.

 

A commonly used equation for calculating voltage drop is:

 Voltage Drop =  (Total Watts x Length of Run) / Cable Constant

Where:

Voltage Drop is the loss in voltage as measured at the end of the cable run

Total Watts is the sum of the wattage of the lamps on the circuit

Length of Run is the length of the wire to the last fixture in feet

Cable Constant is a factor that has been determined for each size of cable:

Wire Size Constant Value Wire Size Constant Value

#18 Wire

1380

#12 Wire

7500

#16 Wire

2200

#10 Wire

11,920

#14 Wire

3500

#8 Wire

18,960

 

Example:

We have 7 fixtures on a circuit, all of which use 20 watt MR16 halogen lamps (total of 140 watts). The length of the run is 90 feet and we want to use #12 wire.

Voltage Drop =  (Total Watts x Length of Run) / Cable Constant

Voltage Drop = (140 watts x 90’) / 7500

Voltage Drop =  12600 / 7500

Voltage Drop =  1.68 volts

 

This is too much because 12 volts – 1.68 volts is 10.32 volts, well under the 10.8 volts that we want to operate halogen lamps. There are several ways to fix this problem as will be discussed below; however if we want to fix it by changing the wire we need to redo the calculation. Let’s try #10 wire:

Voltage Drop =  (Total Watts x Length of Run) / Cable Constant

Voltage Drop = (140 watts x 90’) / 11920

Voltage Drop =  12600 / 11920

Voltage Drop =  1.06 volts

 

This will work because 12 volts – 1.06 volts is 10.94 volts which is more than the 10.8 volt minimum. If we used this deign, the voltage should be measured at the lamp with a digital volt meter when the fixture is installed to confirm that there is adequate voltage.

 

Use the table below as a starting point for determining the wire size for various lighting loads.

Wire size

#12

#10

#8

Feet

Maximum Wattage*

50

225

300

300

100

100

175

225

150

75

100

150

200

50

75

110

250

40

60

90

300

35

45

75

 

* These values assume an equal spacing of the load. If the load is at or near the end of the run, the maximum wattage may have to be reduced. If there are no halogen lamps in the circuit then you may increase the maximum wattage by 10%. Always confirm the actual voltage with a digital volt meter.

  

Methods for reducing Voltage Drop

By looking at the voltage drop formula we can see the factors that affect voltage drop: the load, the length of the run, the voltage at the transformer, and the size of the wire. Therefore if we need to reduce the voltage drop we must change one of these factors.

 

The load in watts can be reduced by changing the lamps to ones with a lower wattage. You can also eliminate a fixture or two or move them to another circuit. Obviously this will have an impact on the intensity of the light and or size of the area that will be lit.

 

The length of the run can be changed several ways. It may be possible to use multiple transformers so that they may be moved closer to the fixtures. By looping back to the transformer from the last fixture you effectively cut the length of the run in half. When using this technique polarity of the cables must be maintained. (SP wire has a rib on one of the conductors so that it is easy to identify. Make sure both ribbed ends are under the same terminal at the transformer.)

 

The size of the wire can be changed by using a larger gauge of wire or by doubling the same size wire. You may also use a large wire such as #8 to get to the area where the fixtures are located and then switch to a smaller gauge for the connection to the fixtures.

 

The first thing to do with the transformer is determine the actual output voltage. Remember the transformer simply reduces the primary voltage by a fixed factor of 10 to produce the output or secondary voltage. If the primary voltage is 130 volts, the output will be 13 volts and voltage drop will be desirable.

 

If the output voltage is 12 volts or less and the length of the run results in excessive voltage drop, you may want to use a multi-tap transformer that has outputs of more than 12 volts. These transformers have terminals that are marked with the higher (and lower) voltages or have a switch used to select the alternative voltages. The type with several terminals allow you to have shorter runs that are not affected by voltage drop receive only 12 volts while the longer runs can be connected to the higher voltage terminals.

 

 Voltage drop can work in your favor as well. Operating the lamp at a lower voltage reduces light output, but it also increases lamp life, particularly with non-halogen lamps. This can be used to your advantage when there are fixtures in the system that are located in difficult to service places such as in tall trees. By selecting a lamp with a higher wattage than required and reducing the voltage to 10.5, the lamp could last 5 times longer than it would if operated at 12 volts.

 

Selection of Transformer and Controls

Once the circuits have been designed you will have the information needed to select the type and number of transformers and their controls. The first step is to add the wattages of all the fixtures that are going to be connected to the transformer. It is recommended that this load be no more than 80% of the maximum output of the transformer. For example if the total load is 341 watts, you divide that by .8 which equals 426 watts. The closest transformer that will handle that load is a 600 watt model. And although 600 watts is almost 75% more that the actual load it is a good selection because there may be the need to add additional lighting after seeing how the design actually works. Also changes in the landscape as the plants mature or the use of the property may change which may require additional lighting later on. We would have to use a combination of smaller transformers to get closer to the actual calculated load. This would cost more than the single larger transformer.

 

 If there are no voltage drop problems and no need to operate the system at a lower voltage for lamp life then there is no need to incur the expense of a multi-tap transformer. Also if the line voltage circuit is controlled by a timer or X10 system there is no need for a timer in the transformer. In that case it may still be advisable to have the transformer controlled by a photocell to keep it from operating too early during the summer when the sun is shinning late into the evening.

 

The location of the transformer is also important in selection. If it is to be located inside it must be approved for indoor use. It must also have the right type of punch outs to accept conduit which is required by code to run the wires through the wall from outside. If a photocell is required then a remote model with a 10’ – 15’ connecting cable will be needed so that it can be in the open daylight.

 

Transformers which will be subject to harsh environments should be constructed of materials that hold up to the elements. Stainless steel cabinets are available at reasonable prices and will resist corrosion better than painted steel. Of course transformers that are to be installed below grade must be designed for direct burial.

 

Wire and Connectors

Your scaled drawing will also be a good starting point for calculating the amount of wire that you’ll need for the installation. Remember, the plan will only help you with the lengths along the ground. You must add the vertical runs like up columns for deck lighting, getting to tree mounted down lights, and up to the transformer. Allow an extra 2 feet of cable for splices and connections. For area and directional lighting add a few feet to make a loop so that the fixture can be moved if necessary. Planning ahead for moves will prevent the necessity of adding a couple of splices later on.

 

You must also go through the circuits in your mind to determine how many and what kind of connectors that will be needed. Most fixtures are shipped with some type of quick connector. For above grade connections they will probably work fine for many years. For below grade connections it may pay to use a sealable type connector. It does not take long for the dampness to cause corrosion which will cause a failure. It frequently takes a long time to find the bad connection. Using a sealable connector when the system is installed will more than pay for the extra cost of trying to find a bad connection later on.

 

Use the same process when figuring out how many fasteners, staples, wire ties, and ground staples, that you will need. If the project involves running wire in trees then add tree mount strapping. There are several types of this strapping that are designed to hold the wire in place without damaging the tree. Fasteners are the least expensive part of the system so buy twice what you need. The extra expense will be less than having to make another trip back to the electrical supply store. Extras can be used for later projects. Add some electrical tape and liquid tape to the list. They always come in handy for any electrical installation.
 

 

 

 

 
Google

© 2006-2008 Ernie Sears. All Rights Reserved.

                                  

                              Hit Counter